Control unit (PCH-RF-T12V)

  • LCD display: temperature, mode, fan speed, output status
  • 6 keys for easy operation
  • Heating, cooling, automatic mode or fan-only operation
  • 3 fixed fan speeds or continuous automatic fan control
  • Powered with 12 V DC from the actuator unit over 2 wires — or from a separate local 12 V DC supply, with no wires to the actuator at all

Actuator unit (PCH-RF-R)

  • DIN rail mounting, 230 V AC supply
  • Wireless link to the control unit — 868 MHz LoRa, up to 50 m
  • Inputs for window switch and external PT1000 thermistor
  • ModBus RTU (terminals A, B) for a central control system
  • Several actuators with one control unit (Master / Slave)

Installation and first steps

  1. Actuator unit: mount it on the DIN rail no more than 30 m from the control unit and connect 230 V, fan speeds, valves, PT1000, ModBus and window switch. 230 V outputs go on the large terminal blocks, 0–10 V outputs on the small ones.
  2. Control unit: fix the mounting plate to the wall (or a flush box) and hook the control unit onto it.
  3. Pair: give every control unit a unique RF address (parameter P25), then hold the hidden button on the actuator and choose “SYNC PARAMS” on the control unit. A green LED next to the antenna confirms the link.
  4. Configure: 77 hidden parameters (P0–P45, D0–D17, T1–T26) adapt the thermostat to 2-pipe or 4-pipe systems and to the fan coil unit — see the installation manual.
PCH-RF-12V dimensions: control unit 135 × 79 × 12 mm, actuator 90 × 95 mm
Control unit 135 × 79 × 12 mm · Actuator 90 × 95 mm, DIN rail
PCH-RF-R actuator terminal layout
Actuator terminals — 0–10 V outputs, ModBus, 12 V out, PT1000, window, Master/Slave
230 V wiring example with fan motor and heating and cooling valves
230 V side — fan speeds V1–V3, heating and cooling valves

General

Actuator power230 V AC
Control unit power12 V DC, 200 mA
RF connection868 MHz (LoRa), up to 50 m
Operating range0–50 °C
Control unit size135 × 79 × 12 mm
Actuator size90 × 95 mm, DIN rail
System2-pipe / 4-pipe fan coil

Actuator inputs / outputs

3 × 230 V / 2 AFan speeds V1, V2, V3
2 × 230 V / 0.5 AHeating / cooling valves (H, C)
1 × 0–10 V DCContinuous fan speed control
2 × 0–10 V DCHeating / cooling valves (H, C)
Window switchOpen window detection
Room occupancyHotel occupancy switch
PT1000Water temperature, 2-pipe systems
ModBus RTUTerminals A, B

Display option

Bright LED display version

The PCH-RF-12V control unit is also available with a bright LED display: crisp white digits on a black front that stay easy to read from across the room and in low light.

Available in black and white versions. It works with the same actuator unit and the same wireless LoRa connection as the LCD model. Ask us about the LED version when you order.

BlackWhiteLED display