Control unit (PCH-RF-TAAA)

  • LCD display: temperature, mode, fan speed, output and battery status
  • 6 keys for easy operation
  • Heating, cooling, automatic mode or fan-only operation
  • 3 fixed fan speeds or continuous automatic fan control
  • Powered by 3 AAA batteries for approx. 1.5 years — no wiring needed
  • Battery indicator on the LCD; shows “Lo bat” when the batteries run out
  • RF transmit power adapts to the distance to the actuator, saving battery

Actuator unit (PCH-RF-R)

  • DIN rail mounting, 230 V AC supply
  • Wireless link to the control unit — 868 MHz LoRa, up to 50 m
  • Inputs for window switch and external PT1000 thermistor
  • ModBus RTU (terminals A, B) for a central control system
  • Several actuators with one control unit (Master / Slave)

Installation and first steps

  1. Actuator unit: mount it on the DIN rail no more than 30 m from the control unit and connect 230 V, fan speeds, valves, PT1000, ModBus and window switch. 230 V outputs go on the large terminal blocks, 0–10 V outputs on the small ones.
  2. Control unit: fix the mounting plate to the wall (or a flush box) and hook the control unit onto it.
  3. Pair: give every control unit a unique RF address (parameter P25), then hold the hidden button on the actuator and choose “SYNC PARAMS” on the control unit. A green LED next to the antenna confirms the link.
  4. Configure: 77 hidden parameters (P0–P45, D0–D17, T1–T26) adapt the thermostat to 2-pipe or 4-pipe systems and to the fan coil unit — see the installation manual.
PCH-RF-AAA dimensions: control unit 135 × 79 × 12 mm, actuator 90 × 95 mm, wireless connection
Control unit 135 × 79 × 12 mm · Actuator 90 × 95 mm · wireless link
PCH-RF-R actuator terminal layout
Actuator terminals — 0–10 V outputs, ModBus, 12 V out, PT1000, window, Master/Slave
230 V wiring example with fan motor and heating and cooling valves
230 V side — fan speeds V1–V3, heating and cooling valves

General

Actuator power230 V AC
Control unit power3 × AAA (1.5 V)
Battery lifeapprox. 1.5 years
RF connection868 MHz (LoRa), up to 50 m
Operating range0–50 °C
Control unit size135 × 79 × 12 mm
Actuator size90 × 95 mm, DIN rail
System2-pipe / 4-pipe fan coil
BatteriesUse only alkaline or lithium AAA batteries. The RF module briefly draws about 120 mA when transmitting, which zinc-carbon batteries cannot reliably supply. Replace all three at the same time.

Actuator inputs / outputs

3 × 230 V / 2 AFan speeds V1, V2, V3
2 × 230 V / 0.5 AHeating / cooling valves (H, C)
1 × 0–10 V DCContinuous fan speed control
2 × 0–10 V DCHeating / cooling valves (H, C)
Window switchOpen window detection
Room occupancyHotel occupancy switch
PT1000Water temperature, 2-pipe systems
ModBus RTUTerminals A, B