Digital room thermostat · 230 V
Controls fan coil units in 2-pipe and 4-pipe systems. Powered directly from the 230 V mains, it drives three fan speeds and the heating and cooling valves, measures the room with its internal sensor or an optional external one, and supports a window switch and day/night mode. Five buttons and an LED display show the mode and fan speed at a glance.
Mounting location
Mount the thermostat on a wall 1.5 m above the floor, where the room temperature is as constant as possible — away from draughts, fan coil units, radiators, stoves, windows and direct sunlight.
Opening the housing and wall mounting
Connections
Buttons
Automatic fan speed control
In heating mode the fan coil runs while the room is at least half the hysteresis below the set temperature, and the valve opens if one is used. In cooling mode it runs while the room is at least half the hysteresis above it. The further the room temperature is from the set value, the higher the fan speed. In 4-pipe systems, heating and cooling change over automatically.
| Supply voltage | 230 V AC / 50 Hz |
| Power consumption | approx. 0.5 W |
| Fan outputs | 3 × 230 V / 2 A |
| Valve outputs | 2 × 230 V / 0.5 A |
| Operating temperature | 0–50 °C |
| Control range | 0–50 °C |
| Front panel | 135 × 75 mm |
| Housing depth | 22 mm |
| Display | 10 × 27 mm |
| N, L | Power supply 230 V AC |
| 1 | Minimum fan speed |
| 2 | Medium fan speed |
| 3 | Maximum fan speed |
| 4 | Heating valve |
| 5 | Cooling valve |
| MAG.ST D.O., GND | Window switch |
| Tset D/N, GND | Day / night mode |
| Sensor (3 terminals) | Internal or external temperature sensor |