Operation

  • LED display for temperature and adjustable parameters
  • 5 buttons for easy operation
  • Heating or cooling (2-pipe system) or automatic heating/cooling changeover (4-pipe system)
  • 3 fan speeds or automatic speed selection
  • LED indication of mode, valves and fan speed

Connections

  • Power supply 230 V AC / 50 Hz, consumption approx. 0.5 W
  • 3 outputs 230 V / 2 A for fan speeds
  • 2 outputs 230 V / 0.5 A for heating and cooling valves
  • Inputs for window switch and day/night mode
  • Internal sensor, or optional external temperature sensor
WarningSwitch off the power supply of the fan coil unit before connecting the thermostat. The electrical connection must be carried out by a qualified person, according to the wiring diagram of the fan coil unit.

Mounting location

Mount the thermostat on a wall 1.5 m above the floor, where the room temperature is as constant as possible — away from draughts, fan coil units, radiators, stoves, windows and direct sunlight.

Opening the housing and wall mounting

  1. Remove the 4 screws on the sides of the housing (2 left, 2 right) and detach the front part from the back part.
  2. Fix the back part of the housing to the wall through its mounting holes.
  3. Connect the wires to the terminals on the front part, as shown below.
  4. Put the front part back onto the wall-mounted back part and secure it with the 4 side screws.
Correct and incorrect mounting locations, 150 cm above the floor
Correct and incorrect mounting locations

Connections

DT-2005/U terminals N, L, 1, 2, 3, 4, 5
Power N, L · fan speeds 1–2–3 (min–max) · valves 4 heating, 5 cooling
Internal temperature sensor and connection of the external sensor
Remove the internal sensor; connect the external one brown–white–green from the housing edge
Window switch and day/night inputs on the mini terminals
Window switch: MAG.ST D.O. + GND · Day/night: Tset D/N + GND

Buttons

  1. Up / down set the desired room temperature from 0 to 50 °C; the value flashes while you set it.
  2. ON/OFF switches the fan coil unit on or off and cancels an entered value.
  3. Fan selects fan speed 1, 2, 3 or automatic (A) and confirms entered values.
  4. Sun / snowflake switches between heating (2-pipe), cooling (2-pipe) and automatic (4-pipe).
Meaning of the display symbols and LEDs
Meaning of the symbols and LEDs

Automatic fan speed control

In heating mode the fan coil runs while the room is at least half the hysteresis below the set temperature, and the valve opens if one is used. In cooling mode it runs while the room is at least half the hysteresis above it. The further the room temperature is from the set value, the higher the fan speed. In 4-pipe systems, heating and cooling change over automatically.

Automatic fan speed switching for heating
Heating — fan speed vs. room temperature
Automatic fan speed switching for cooling
Cooling — fan speed vs. room temperature

Technical data

Supply voltage230 V AC / 50 Hz
Power consumptionapprox. 0.5 W
Fan outputs3 × 230 V / 2 A
Valve outputs2 × 230 V / 0.5 A
Operating temperature0–50 °C
Control range0–50 °C
Front panel135 × 75 mm
Housing depth22 mm
Display10 × 27 mm

Terminals

N, LPower supply 230 V AC
1Minimum fan speed
2Medium fan speed
3Maximum fan speed
4Heating valve
5Cooling valve
MAG.ST D.O., GNDWindow switch
Tset D/N, GNDDay / night mode
Sensor (3 terminals)Internal or external temperature sensor